1.0 INTRODUCTION
While the most important function of any
variable air volume (VAV) system is to provide a high quality environment for
building occupants, this critical function rarely receives the attention it
deserves. As a result, basic control strategies for terminal VAV boxes have
seen little significant change since the introduction of pressure independent
box control more than 30 years ago.
However, by applying more effective operating
strategies available with modern digital controls, designer can offer enormous
improvements in building comfort and occupant control enhancement that will
improve the comfort and climate in
commercial buildings.
2.0 VAV SYSTEM
2.1 DISCRIPTION:
VAV systems are designed
to supply only the volume of conditioned air to a space that is needed to
satisfy the load. Fan energy is saved when the volume of air handled by the fan
is reduced. Air volume control is accomplished by installing modulating
dampers, or in some cases, an air valve, in the supply duct to each zone. As
the room temperature demand becomes satisfied, the thermostat signals the
damper to move the supply air zone valve toward the closed position.
When zone valves are
throttled, the static pressure in the supply duct changes. A static pressure
sensor located in the supply duct senses the static pressure change, and either
increases or decreases the airflow from the source, using variable speed
control or dampers on the main air supply fan.
A key component in the
VAV system is the air valve. It is commonly installed inside an insulated sheet
metal box suspended in a ceiling plenum. The air valve has a damper that
regulates the airflow in response to the room's thermostat. A multi-port
pressure-sensing ring provides both accurate airflow sensing and control in
response to duct static pressure. As VAV systems have evolved, so have the
terminals. There are six popular VAV systems. They are:
·
Shutoff
·
VAV Reheat
·
Parallel Fan Powered
·
Series Fan Powered
·
Dual Duct
·
Changeover/Bypass
2.2 APPLICATION CONSIDERATION:
There are many factors to
consider when designing VAV systems. Here are a few:
1.
VAV systems are
popular because they can easily accommodate added control zones.
2.
Small zones contribute
to precise temperature control, which facilitates occupant comfort. However,
the costs increase with the number of zones.
3.
Air distribution by
diffuser at varying velocities is another important consideration with VAV
systems.
4.
One method of
increasing zone airflow during light cooling loads is to design an intelligent
control scheme that resets the leaving air temperature off the coil upward.
This method will circulate more air at higher temperatures, and will save
energy.
5.
Building pressure
control is especially important in VAV systems. The exhaust fan is modulated,
as necessary, to maintain a fixed, slightly positive space pressure.
2.3 TYPES OF VAV SYSTEM:
2.3.1 REHEAT VAV:
This system is generally
used in cooling-only applications, that is, areas not normally needing heat
during occupied hours. Where significant skin heating loads are common,
perimeter radiant heat is added under windows to prevent cold down drafts.
Instead of locating heat
within the zone, a VAV reheat system places heat within the VAV terminal, most
commonly in the terminal's outlet. The heat can be
supplied by hot water, steam or an electric coil.
To ensure sufficient airflow, the air valve
damper will typically have an adjustable minimum stop. This system type is
often selected when system first cost is a primary driving force.
2.3.1.1 REHEAT VAV – ADVANTAGES:
1.
The major equipment is
centrally located. This permits operation and maintenance to take place outside
of occupied areas.
2.
Temperature control
for even a large number of zones is relatively inexpensive. Plus, this system
can accommodate simultaneous heating and cooling. Heating and cooling coils
won't be fighting each other.
3.
It's very flexible.
The system can be subdivided or expanded into new zones to fit building
remodeling or additions easily and inexpensively.
4.
This system can save
money by:
- Modulating the fans. Fans consume a significant portion of the energy in the building, and VAV system fans run at substantially lower volumes most of the time. This offers the potential for significant energy savings.
- Taking advantage of a building's heating and cooling diversity. This can lower the system's first cost, as well as reduce energy consumption because it is using smaller equipment at more efficient part-load conditions.
- And, isolating and shutting down unoccupied areas of the building.
5.
Since the system will
most often operate below the design condition, noise levels will usually be
lower than specifications.
6.
VAV boxes with high
minimum stops may be ideal for areas where constant airflow and
dehumidification are required.
2.3.1.2 REHEAT VAV – DISADVANTAGES:
1.
Accessibility to
terminal units is important. This means architects and mechanical and
structural designers must carefully coordinate their work.
2.
Each terminal unit has
an air valve, which requires either electrical or pneumatic service.
3.
Each terminal unit has
a heating coil, which requires utility service and maintenance.
4.
The system requires
diffusers that can provide adequate distribution characteristics over a wide
range of airflows.
5.
During the heating
mode, the primary airflow is first cooled and then reheated resulting in
increased energy consumption.
2.3.2 PARALLEL FAN POWERED VAV:
The parallel fan powered
VAV terminal is a common system design. In this configuration the cooling air
valve is first modulated to a predetermined minimum position (it can be
completely closed). Then the terminal fan and heat are energized consecutively
as the temperature in the space continues to drop. In this configuration, the
primary air does not pass through the terminal unit's fan.
When no heat is needed,
the local parallel fan is off and a back draft damper is closed to prevent cool
air entry into the return plenum. When little or no air is flowing to the VAV
zone, and the zone temperature drops below set point, the local parallel fan is
turned on and the back draft damper opens. Warm recirculated plenum air is then
mixed with the minimum flow of cool primary air and delivered to the zone at a
predetermined minimum constant air volume. Additional heat can also be
provided, when specified, by a heating coil located at the leaving airside of
the unit.
A major benefit of
parallel fan powered terminal units is that the secondary fan motor runs only
when primary air tempering is required. Also, the terminal fan requires no
special interlock with the central air handler because it sits outside the
primary air stream. Another benefit is that the heat of the plenum (due mainly
to lighting) can be used for zone tempering.
2.3.2.1 PARALLEL FAN POWERED VAV – ADVANTAGES:
1.
The major equipment is
centrally located.
2.
Temperature control
for even a large number of zones is relatively inexpensive. Plus, this system
can accommodate simultaneous heating and cooling. Heating and cooling coils
won't be fighting each other.
3.
The fan powered VAV
box can take advantage of the heating effect of lights to reduce building
heating requirements.
4.
It's very
flexible.
5.
This system can save
money by:
o
Modulating the fans.
- Taking advantage of a building's heating and cooling diversity.
- And, isolating and shutting down unoccupied areas of the building.
6. Since the majority of the operation will be below design conditions, the noise level will often be lower than specified at design.
2.3.2.2PARALLEL FAN POWERED VAV– DISADVANTAGES:
Accessibility to
terminal units is important. This means architects and mechanical and
structural designers must carefully coordinate their work.
1.
Each terminal unit has
a fan and filter, which require electric service as well as periodic
maintenance.
2.
Each terminal unit has
an air valve, which requires either electrical or pneumatic service.
3.
The system requires
diffusers that can provide adequate distribution characteristics over a wide
range of airflows.
2.3.3 SERIES VAV:
Series fan powered
terminal units are commonly used in VAV zones that not only require heat during
occupied hours, but also constant volume air delivery. With this system the
terminal unit fan is in series with the central fan. Therefore, primary air
from the central fan always passes through the terminal unit fan. The local
series fan is generally sized for 100 percent zone airflow since all primary
airflow passes through it. This secondary fan operates whenever there is a call
for airflow to the zone. This ensures a constant flow of air, but the
temperature of the air varies.
As the zone is cooling
requirement decreases, the valve's damper closes. As the damper closes, the air
mixture supplied to the zone contains less cool air and more warm recirculated
plenum air. The heating coil located at the leaving airside of the unit can
provide additional heat.
Series fan powered
terminals are often selected due to the advantage of constant air delivery to
the zone, while still benefiting from the energy saving associated with VAV at
the main air handler. Series terminal may be used throughout the entire
building or they may be selectively applied in areas where constant airflow is
desirable, such as washrooms, entranceways, hallways, atriums, and conference
rooms.
2.3.3.1 SERIES VAV –ADVANTAGES:
1.
The major equipment is
centrally located.
2.
Temperature control
for even a large number of zones is relatively inexpensive. Plus, this system
can accommodate simultaneous heating and cooling. Heating and cooling coils
won't be fighting each other.
3.
The fan powered VAV
box can take advantage of the heating effect of lights to reduce building
heating requirements.
4.
It's very flexible.
5.
This system can save
money by:
o
Modulating the fans.
- Taking advantage of a building's heating and cooling diversity.
- And, isolating and shutting down unoccupied areas of the building.
6.
Since the majority of
the operation will be below design conditions, the noise level will often be
lower than that specified at design.
2.3.3.2 SERIES VAV – DISADVANTAGES:
- Accessibility to terminal units is important. This means architects and mechanical and structural designers must carefully coordinate their work.
- Each terminal unit has a fan and filter, which require electric service as well as periodic maintenance.
- Each terminal unit has an air valve, which requires either electrical or pneumatic service.
2.3.4 DUEL DUCT VAV:
Dual duct terminals units
have two air valves in a common VAV box enclosure: one controls cool primary
air and the other controls warm air. This system provides variable air volume
as well as variable temperature. With the dual duct system, adjustable air
mixing point is provided to minimize air movement when the unit changes over
between cooling and heating, and vice versa. Terminals are connected to
temperature sensors located in the zone.
Dual duct systems can be
very energy efficient when there is little call to mix cool and heated air, and
separate supply fans are utilized for heating and cooling. A major shortcoming
of single-zone systems is that the heating and cooling capacity supplied to
each comfort zone cannot be adjusted to match changing load conditions within
the zone. As a result, although the central thermostat can be satisfied,
individual zone comfort is often compromised.
2.3.5 CHANGEOVER/BYPASS VAV SYSTEMS:
When first cost is key,
the changeover/bypass systems can provide temp. Control to each zone in the
building, while using a typical single-zone air conditioning unit. This system
is called changeover/bypass because it changes over between heating and cooling
operation and uses a bypass loop to allow constant volume fans on air
conditioning equipment while delivering variable air volume to the zone. Many
single-zone applications utilize direct expansion refrigeration systems that
will not tolerate large reductions in airflow. A central system controller
monitors the heating and/or cooling needs of all comfort zones and
automatically changes system operation from heating to cooling, or vice versa
as necessary, to satisfy the needs of the zones. Instead of using a single-zone
sensor to determine heating or cooling, each zone has a thermostat.
The central system
controller can be programmed to weight zones in order of importance to decide
if the central air conditioning unit should be providing heating or cooling.
The central system controller also senses the supply airflow rate and modulates
a supply air bypass damper to maintain the required airflow through the air
conditioning unit. The air terminal unit used with this system is similar in
function to the shutoff terminal. The unit controller is typically connected to
a zone thermostat that provides input for the zone controller to modulate the
zone control damper.
2.3.5.1 CHANGEOVER/BYPASS VAV SYSTEMS
- APLLICATION CONSIDERATIONS:
A changeover/bypass VAV
system has many of the same application guidelines as the more traditional VAV
systems. However, there is one additional consideration, thermal zoning. A
changeover/bypass VAV system cannot accommodate simultaneous cooling and
heating demands on the same unit, For applications requiring heat on demand
when the air conditioning unit is in the cooling mode, duct heating coils can
be installed and controlled from the zone damper controller and zone
thermostat.
This does not limit this
system to small buildings. Larger office buildings, schools, and manufacturing
facilities can be served as long as the building can be thermally zones to
accommodate the systems capabilities, i.e. zones should have similar thermal
loading characteristics. Each thermal zone is then assigned a heating and
cooling unit, which serves a number of individua1 changeover/bypass VAV
terminals.
3.0 VAV ZONE
CONTROL:
VAV systems use
terminal VAV boxes that typically serve zones consisting of two or more offices
or open areas of five or more occupants. The average VAV zone size in
commercial office buildings is usually between 500 and 800 sq ft. in areas, and
most zones are controlled with a single space
temperature sensor. This space temp sensor regulates the flow of primary air
from the VAV box in response to space temperature compared to a zone
temperature set point. Pressure independent VAV box controls modulate the
airflow in range bounded by minimum and maximum airflow rates. Many VAV systems
are designed to operate with a fixed supply air temperature (usually 13ºC), or
with a supply air temperature reset over a limited range (e.g.13 ºC to 15.
5ºC). Fig. 1 & 2 show typical VAV zone configurations used in commercial
building. In fig.1 VAV box serves perimeter offices and in fig.2 it serves open
office area. In both figures, a single temperature sensor is used to control
the VAV box. Occupancy sensors may exercise lighting control as shown in figure
1 & 2, by wall switches, or by a separate digital lighting control system.
Regardless of the method of lighting control, it is most commonly completely
separate from HVAC control at the zone
level as shown in figures 1 & 2.
As they lay out
VAV zones, designers should be mindful that comfort issues continue to be the
no one complaint occupants have about their office space. Furthermore, actual
thermal conditions in large areas of commercial buildings are often outside
accepted comfort limits. Simple steps that can improve zone comfort should
always be considered. The layouts in figures 1 &2 have many problems that
can adversely affect comfort and can be mitigated with improved controls.
Location of the
temperature sensors for each VAV box is a common problem. In office areas, the
largest or more representative office usually is chosen. In open areas without
fixed partitions, a nearby wall or building column as shown in fig. 2 is
generally selected. Using only a single temperature sensor for multiple offices
risks extended periods of poor comfort in the offices without sensors. Offices
are often located around perimeter of the building. When VAV systems were first
introduced, the building envelope dominated the variability of thermal loading
of these spaces. So long as long offices were on the same exposure, a single
sensor was adequate to regulate conditions in all the offices because the
thermal load was expected to be pretty much same for all the offices due to
their common exterior exposure. That logic is no longer valid for modern
designs Envelop losses have been much reduced in recent years. While lighting
loads and many office appliance loads have also decreased, the density of
people and appliances in offices has generally increased, and the variability
in internal loads among offices is far greater due to improved local controls
such as occupancy sensors for lighting and standby modes for office equipments.
Imagine an
occupant is away for the day & the temperature sensor is located in his or
her office (fig 1). The office is vacant with lights off & door &
Window blinds close. It is likely the other offices will be out of acceptable
comfort range & their occupants will have comfort complaints during that
day due to the significant variance of heat loads in those spaces compared to
the one in witch the sensor is located.
Another problem
is the isolation of the HVAC& lighting systems typical of most building
controls. In fig1&2, the lights will react promptly to occupancy. However,
because of building thermal inertia & the nature of zone controls,
substantial portion of a building must become unoccupied for long periods
before the reduced cooling load leads to a reduction in HVAC energy. This
wastes energy & leads to discomfort from swings & variations in
temperature throughout the building. Furthermore, no mechanism exists to direct
comfort cooling resources specifically to the areas of the building that are
occupied.
Cool & cold
weather operation also can cause comfort problems. Unless fan-powered VAV box
or high minimum airflows are used, “dumping” often occurs at low cooling load
conditions. Dumping occurs if diffusers are not carefully selected for the
minimum flow and the flow among the diffusers is not kept in balance. In such
conditions, the lower temp primary air fails to mix with room air due to the
low exit velocities from the diffuser at minimum flow conditions. Without
mixing, the dense primary air falls directly on the occupants, causing
discomfort. Even when dumping does not occur, the low supply airflow may cause
supply air to inadequately mix with room air. Comfort problems associated with
VAV systems have become more pronounced in the last decade.
4.0 DESIGNING MORE EFFECTIVE VAV ZONE
SYSTEM:
Research and testing has shown that operating VAV systems
with a minimum supply temp of 10°C that is adjusted upward when
cooling demand falls usually results in a much more efficient and cost
effective system than employing a fixed 13°C supply air temp.
Field experience indicates when the controls of poorly performing VAV systems
are reconfigured with optimization control to maximize operating efficiency
under all condition; the result is a supply air temperature that changes with
cooling load. Such optimization frequently yields the lower supply air
temperatures suggested by this research along with reduced airflow at peak load
Conditions.
Freely
optimized controls of conventionally designed systems yield supply air
temperature that usually vary from about 10°C to 16°C. This optimized operation with adjustable or floating
supply air temp. Offers improved comfort conditions due to greater air circulation
& less risk of dumping during cooler weather, which leads to more uniforms
space conditions at all times. Also, lower temp air may be used to reduce in
door humidity during humid outdoor conditions. Finally for many system type,
the implication of floating supply air temp strategies significantly improves
the energy performance of the over all comfort system.
When VAV systems are designed with adjustable or floating
supply air temp control strategies, thought has to be given to how the VAV
zones and boxes are sized. Currently, VAV boxes usually are sized based on a
singe point of operation: maximum zone load at designed supply air temp.
However, we can adjustable supply air temp and optimized control, the greatest
zone airflow requirement may not occur at pick load conditions. Table 1 shows
air flow requirements at various load conditions for typical zones in a VAV
system with adjustable supply air temp .The figures ware developed assuming the
same pick load for each zone. Airflows have been calculated by first estimating
the highest supply air temp that could occur at 70% zone cooling load and that
air flow requirement at this load point is about 25% greater than at peak load.
For interior zones, the peak airflows requirement is about 40% greater than at
designed conditions.
When designing for adjustable or floating
supply air temp, the designer needs to develop charts like these for typical
perimeter and interior zones. Then, designers must size VAV boxes that serve
those zones for the highest airflow that may be required. While the supply air
reset scheme should be developed so that the peak airflow demand can always
satisfy the building, some areas of the building may require higher airflows
under non-design conditions when the supply air temp has been reset upward.
Designers also need to take care when sizing
system duct work and zone components to ensure that they are adequate to
provide properly distribute the require air flow at park load conditions when
the supply air temperature may be above the minimum. Unless the reset scheme is
developed carefully to minimize the higher part load air flow requirements in
areas of the building, the potential savings from smaller size fan and duct
work possible with the lower design supply air temperature can be compromised.
When a VAV
system with adjustable supply air temperature is used, the control of the VAV
box dampers must also be given special attention. Control of the primary air
damper is typically bounded by preset minimum and maximum airflows, and the
airflow set point is based on space temperature vs. Set point for the zone. The
minimum airflow rate is usually based on outdoor air ventilation requirements.
However, when the outside air content of the primary air stream and the temperature
of the primary supply air are both design to be variable, neither of these air
flow limits nor the damper control algorithm should be fixed. Instead the box
maximum and minimum and damper control can be continuously calculated and
adjusted based on the status of the space served, the percent outside air in
the primary air stream, and the temp of the primary air. Such calculation and
adjustment can be easily made since the information required to make such
adjustments is readily available over the control network. The resulting box
damper control for the South Perimeter zone analyze in table 1 is shown in
figure 3.
Figure 3
illustrates the use of “cooling effect” damper control to replace conventional
box damper control when proportional-only control is used to modulate airflow
with respect to space temp error from set point. However, the technique also
can be used when full PID or other control techniques are applied to modulate
the VAV box damper. Cooling effect control results in more stable VAV system
operation and better comfort stability throughout the building when adjustable
primary air temp is used because it maintain a constant rate of cooling into
those VAV zones that are in balance while supply air temp is changing.
5.0
INTEGRATING TEMPERATURE AND OCCUPANCY CONTROL:
Upgrading VAV system design with adjustable
supply air temp and “cooling effect” control of VAV boxes has the potential to
yield large zone comfort improvements. Today’s high level and low cost of
control technology is a mandate for designer to do much more to promote comfort
in commercial buildings. The use multiple pace temp sensors to control each VAV
box has been shown to be an effective and low cost upgrade to VAV terminal
control. Consider the benefit of adding space temp sensors in each of the zones
represented in the fig 1 and 2. In fig 1,adding temp sensors in the other two
offices would permit the conditions in those offices to be incorporated in the
control of VAV box and lead to generally more comfortable conditions in the
office spaces.
In open office areas, multiple temp sensors
also are helpful in improving comfort conditions. When fully configured and
occupied, modular partitions and variation in loading often make the addition
of space temp sensors helpful in open office areas. Also, it is often difficult
to locate sensors optimally in open offices. Multiple sensors can help achieve
more uniformly comfortable conditions throughout large office areas. For the
open office area in fig 2, adding another temp sensor on the building column on
the left may improve the comfort level in that zone.
However, the real benefits of improved sensing
are most effectively realized when lighting and occupancy controls are
incorporated along with additional temp sensors. Consider fig 4 and 5 in which
the occupancy sensing and lighting control has been integrated into the VAV
zone control along with additional temp sensors. The result is the development
of “sub zones,” each of which has individual temp and occupancy sensing and
lighting control. These “sub zones” permit a substantial increase in the level
of comfort in buildings.
Consider the example cited earlier in which the
large office in fig 1 is unoccupied. In the fig 4 configurations, the unoccupied
condition of that office is included in the box control as well as the lighting
control logic. Thus, not only is the lighting shut down in that office, but
also the temp sensor in the office is removed from the zone comfort control
algorithm. Only the temps of occupied offices (or open areas) are included in
determining the box cooling effect required for the zone, leading to better
comfort in the occupied spaces. If all three offices are become unoccupied, the
box minimum airflow limit can be reduced or eliminated depending on conditions,
and the cooling effect reduced to keep the offices in a “standby” condition to
await the return of the occupants.
Integrating lighting and comfort control as
shown in fig 4 and 5 can substantially improve building comfort at a small
cost. Consider that the only additional devices required for the zone layouts
shown in fig 1 and 2 are the extra space temp sensors. The occupancy sensing
and lighting controls are already included in the fig 1 and 2 designs-they are
just configured differently than in those designs. The primary change from fig
1 and 2 to fig 4 and 5 is from application-specific controllers with simple,
fixed functions on each VAV box to programmable custom application controllers
that permit each zone to adequately accommodate the number and variety of “sub
zones” it serves. This change to more functional box controllers is fundamental
to success of improving zone control.
6.0 ROLE OF INTEROPERABILITY IN IMPROVING ZONE
CONTROL:
The primary purpose of interoperability at the
zone level is to provide grater choice for the zone control in each tenant’s
space. Many DDC system manufacturers have a limited selection of controllers
for zone control. Some offer only application specific controllers that lack
the programming flexibility to implement cooling effect airflow control or to
implement multiple “sub zones” with integrated lighting control. To improve the
lighting and comfort control options available for building tenant’s, designers
needs to specify and ensure the implementation of a true standard communication
network at the zone level in order to broaden the zone controls choice to a
variety of custom application control products that can be applied for zone
control. Many new products incorporate standard communications such that they
can interoperate with system of various manufacture, offer flexible
programmability and incorporate sufficient I/O capabilities to work well in
integrated lighting /comfort control strategies. Using recognizes standard for
the zone communication network permits different zone control products of
various manufacture and capabilities to serve the needs of individual tenants
in multi-tenants buildings.
Some never zone
control products include a dedicated “sub network” for connecting sub zone
devices such as occupancy sensors, temp sensors and lighting ballasts. This sub
network approach to zone integration is shown in fig 6. Less wiring is involved
in the sub network approach. Its costs compared to the hardwired solutions
illustrated earlier depend on factor such as the levels of occupant interface
and function that are desired from the sub network.
The use of sub network to connect the temp and occupancy
sensors has a number of advantages compared to allocating a separate I\O point
on the box controller for each device. Comparing fig 6 to fig 4 for show that
the wiring is somewhat simpler. More important is the potential for additional
device functionality. For example, a network-connected temp sensor may easily
and in expensively in corporate user interface buttons and a display that
permits the occupant to operate lighting independently of the occupancy sensor
or to adjust the temp set point. With such network- connected devices, light
can be shutdown for presentations, or dimming ballast lighting can be used to
set the lighting level.
While the zoning shown in the figures does not provides
true individuals control of thermal conditions in each sub zone, these simple
configurations provide the ability for individuals occupants to express thermal
comfort preferences, which are then consider by logic in the VAV box controller
in establishing the cooling effect to be delivered to the zone. These
“preference adjustments” will soon be accomplished over networks connected to
the occupants ’PCs. But for the presents, a network connected local temp sensor
device that incorporates pushbuttons and a small display is a simple, low-cost
method of effectively connecting occupants to their environments to improve occupant
comfort.
7.0COST
IMPLICATIONS OF INTEGRETED
ZONE CONTROL:
VAV zone control
cost can vary substantially among buildings, but traditional zones control
generally cost about $1.5 per sq feet in class “A” office building. Code
compliant lighting controls about another $1 per sq feet. When VAV and lighting
control is intergraded according to confirmations shown in fig 4 through 6, it is often possible to
provide the superior environment and individual preference adjustment
capabilities for a premium of as little $0.5 sq feet. This small premium can
pay very substantial rewards for building owners in terms of attracting and
retaining tenant’s.
However,
most enticing to the building owners is that the decision as to whether or not
the cost is justified can be made on a tenant-by-tenant or zone by zone basis,
and the premium can be included as a tenant cost. If the VAV system is designed
with and effective adjustable or floating supply air temp controls strategy and
with a zone control communication network that employees established
communication standards, there is no need to incorporate a single HVAC and
lighting control scheme in every zone. Rather, integrated lighting and HVAC
with individual thermal and lighting level preference adjustment may be applied
only where their applications will compare additional value for the tenant to
justify its cost.
8.0 SUMMARY AND CONCLUSION:
VAV zone control strategies have not changed
significantly in recent years, so change in overdue. To enhance energy
optimization and comfort, and to make the important move toward connecting
occupants with their comfort system, designers need to consider in corpora ting
adjustable supply air temp and recognized standard control communications
trunks in their VAV system design. Implementing a VAV system with adjustable
supply air temp permits the use of a smaller air distribution system that saves
cost without compromising building comfort or operating efficiency.
Implementing zone control on a recognized standard network allows building
owners and tenants to select from a growing variety of options for zone control
that may include sub zone operation and individual preference adjustments. Once
such a system is installed, it is up to the designer to help the building owner
and tenants to select the right mix of lighting integration, occupant
interface, and zone sensing to fit each zone control application.
No comments:
Post a Comment